Data centers are growing, fueled by the proliferation of media,
virtualization and the need for more security and storage. This creates
a high demand for 40 Gbps+ fiber links. Whether it is using 10 Gbps
pre-terminated fiber trunks or planning for next-generation 40/100 Gbps
performance, data centers are standardizing on Multi-fiber Push-on (MPO)
connector solutions.
“SCAN ALL” Function: Scan All function in the MultiFiber Pro Power Meter
automatically scans and tests all 12 fibers in MPO connectors taking
just 6 seconds to complete all loss or power measurements. This feature
automates the testing of MPO terminated fibers and eliminates the time
consuming and manual process of moving the tester from fiber to fiber
while using fan-out cords.
Built-in Polarity Verification: The simple purpose of any polarity
scheme is to provide a
continuous connection from the link’s transmitter to the link’s
receiver. For array connectors, TIA-568-C.0 defines three methods to
accomplish this. The polarity measurement of MultiFiber Pro allows the
user to test individual patch cords, permanent links, and channels for
correct polarity.
On-board MPO connector: The MPO connector on both the OPM and OLS
eliminates the use of costly & complicated fan-out cords to test MPO
fiber trunks.
Simple User Interface: Simplifies the task of simultaneously presenting
polarity, power, and loss results for 12 fibers. The power meter enables
the users to easily comprehend the measurement results of 12 fibers
simultaneously. The light source identifies each fiber within the MPO
connector being tested. Any individual measurements that fail the test
limit is identified to allow root-cause analysis. This powerful yet
straightforward test set enables everyone to become a fiber testing
expert increasing efficiency in testing data center projects.
Select an Individual Fiber: Drilling down to a single fiber during
testing and troubleshooting is always a challenge in data centers.
MuliFiber Pro can troubleshoot a single fiber within an MPO trunk to
provide a single fiber test result. This increases MPO connector
verification and troubleshooting flexibility with more precise
reporting.
|
Environmental |
|
Operating temperature |
-10ºC to +50ºC |
|
Storage temperature |
-20ºC to +50ºC |
|
Operating humidity |
95% (10ºC to +35ºC)
non-condensing |
75% (35ºC to +45ºC)
non-condensing |
Uncontrolled <10ºC |
|
Operating altitude |
4,000 m |
|
Storage altitude |
12,000 m |
|
Vibration Random |
2 G, 5 Hz to 500 Hz |
|
Optical Power Meter (Specifications apply at 23ºC (73ºF), unless otherwise noted.) |
- |
Detector type |
InGaAs |
- |
Calibrated wavelengths |
850 nm, 1300 nm, 1310
nm, 1550 nm |
- |
Measurement range |
0 dBm to -50 dBm |
- |
Power measurement linearity |
±0.1 dB1 |
- |
Power measurement uncertainty |
±0.35 dB |
- |
Power measurement repeatability |
< 0.10 dB |
- |
Display resolution, dB or dBm |
0.01 |
- |
Power display units |
dBm, mW, μW |
- |
User-selectable limit for loss |
0.05 dB to 50.0 dB, in increments of 0.05 dB up to 10.0 dB and 0.1 dB up to 50.0 dB |
- |
Auto wavelength detection |
Yes |
- |
Polarity detection |
Detects A, B, C, and
Corning Plug & Play™ Universal Systems polarities |
- |
2 kHz detection |
Yes |
- |
Record storage |
3000 records, one fiber per record (250 12-fiber cables) |
- |
External interface |
USB 2.0, full speed |
- |
Optical connector |
MPO interface for
12-fiber, unpinned plugs. Compatible with 62.5 μm, 50 μm, and
singlemode fibers. Connector has a self-closing, protective cover. |
- |
Power requirement |
2 AA alkaline batteries |
- |
Battery life2 |
>30 hours (typical) |
- |
Automatic power-off |
10, 20, 30, or 60 minutes (can be disabled by the user) |
- |
Low battery warning |
Low battery icon blinks |
- |
Size |
5.7 in x 3.2 in x 1.5
in |
- |
Weight |
10.9 oz (309 g) |
|
850nm
Source (Specifications apply at 23ºC (73ºF), unless otherwise noted) |
- |
Emitter type LED: |
850 nm |
- |
Wavelength 850 nm: |
±30 nm |
- |
Spectral width (FWHM) |
850 nm: +/- 50 nm
(typical) |
- |
Output power 850 nm: |
≥24 dBm. Max
difference between channels +/-1dB |
- |
Power output stability3 |
≤ ±0.1 dB over 8 hours |
- |
Encircled flux |
Meets ANSI/TIA-526-14-B, ISO/IEC 14763-3, and IEC 61280-4-1 for 50/125 μm at the source’s optical connector. |
- |
Optical connector |
MPO interface for 12-fiber, unpinned plugs. Compatible with 62.5 μm and 50 μm. |
- |
Modes 2 |
kHz modulated, auto wavelength |
- |
Power requirement |
2 AA alkaline batteries |
- |
Battery life4 |
>30 hours (typical) |
- |
Automatic power-off |
10, 20, 30, or 60 minutes (can be disabled by the user) |
- |
Low battery warning |
Low battery icon
blinks |
- |
Size |
5.6 in x 3.2 in x 1.6
in |
- |
Weight |
10.9 oz (309 g) |
|
|